homeapartmentpencilmagic-wanddroplighterpoopsunmooncloudcloud-uploadcloud-downloadcloud-synccloud-checkdatabaselockcogtrashdiceheartstarstar-halfstar-emptyflagenvelopepaperclipinboxeyeprinterfile-emptyfile-addenterexitgraduation-hatlicensemusic-notefilm-playcamera-videocamerapicturebookbookmarkuserusersshirtstorecarttagphone-handsetphonepushpinmap-markermaplocationcalendar-fullkeyboardspell-checkscreensmartphonetabletlaptoplaptop-phonepower-switchbubbleheart-pulseconstructionpie-chartchart-barsgiftdiamondlineariconsdinnercoffee-cupleafpawrocketbriefcasebuscartrainbicyclewheelchairselectearthsmilesadneutralmustachealarmbullhornvolume-highvolume-mediumvolume-lowvolumemichourglassundoredosynchistoryclockdownloaduploadenter-downexit-upbugcodelinkunlinkthumbs-upthumbs-downmagnifiercrossmenulistchevron-upchevron-downchevron-leftchevron-rightarrow-uparrow-downarrow-leftarrow-rightmovewarningquestion-circlemenu-circlecheckmark-circlecross-circleplus-circlecircle-minusarrow-up-circlearrow-down-circlearrow-left-circlearrow-right-circlechevron-up-circlechevron-down-circlechevron-left-circlechevron-right-circlecropframe-expandframe-contractlayersfunneltext-formattext-format-removetext-sizebolditalicunderlinestrikethroughhighlighttext-align-lefttext-align-centertext-align-righttext-align-justifyline-spacingindent-increaseindent-decreasepilcrowdirection-ltrdirection-rtlpage-breaksort-alpha-ascsort-amount-aschandpointer-uppointer-rightpointer-downpointer-left

Distributor spaces in the standards

EN 50174 contains a lot of specifications of distributor spaces, from the room size, the free space in front of and behind cabinets and the technical equipment inside of rooms that hold the distributors. Here’s a simple list where the most important specs of distributor spaces in IT cabling can be found:

 

Size of the room where distributors are located:

  • in office premises: EN 50174-2:2018-10, chapter 8.3.8
  • in industrial premises: EN 50174-2:2018-10, chapter 9.3.8 (points to chapter 8.3.8 of the same standard)
  • in homes: EN 50174-2:2018-10, chapter 10.3.8
  • in apartment buildings: EN 50174-2:2018-10, chapter 13.3.8
  • in data centres: EN 50174-2:2018-10, chapter 11.3.8
  • for distributed building services: EN 50174-2:2018-10, chapter 12.2.8

 

Height of the ceiling:

EN 50174-2:2018-10, chapter 4.9.2.1

 

Door width/height:

  • in office premises: EN 50174-2:2018-10, chapter 8.3.8.2.4
  • in industrial premises: EN 50174-2:2018-10, chapter 9.3.8 (points to chapter 8.3.8 of the same standard)
  • in data centres: EN 50174-2:2018-10, chapter 11.3.8.1.3
  • for distributed building services: EN 50174-2:2018-10, chapter 12.2.8.2.2 (points to chapter 8.3.8.2.4 of the same standard)

 

Locking of the room:

  • demarcation rooms: EN 50174-2:2018-10, chapter 4.9.2.3
  • in office premises: EN 50174-2:2018-10, chapter 8.3.8.2.4
  • in industrial premises: EN 50174-2:2018-10, chapter 9.3.8 (points to chapter 8.3.8 of the same standard)
  • in data centres: EN 50174-2:2018-10, chapter 11.3.8.1.3

 

Raised floor:

  • general: EN 50174-2:2018-10, chapter 4.3.2.2, chapter 4.4.2.1and chapter 4.5.3.1
  • cable pathways: EN 50174-2:2018-10, chapter 4.3.1.4
  • in office premises: EN 50174-2:2018-10, chapter 8.3.8.1.3
  • in industrial premises: EN 50174-2:2018-10, chapter 9.3.8 (points to chapter 8.3.8 of the same standard)
  • in data centres: EN 50174-2:2018-10, chapter 11.3.8.2.4

 

Free space in front of/behind racks and cabinets:

  • in office premises: EN 50174-2:2018-10, chapter 8.3.8.1
  • in industrial premises: EN 50174-2:2018-10, chapter 9.3.8 (points to chapter 8.3.8 of the same standard)
  • in data centres: EN 50174-2:2018-10, chapter 11.3.8.1.3 and chapter 11.3.8.2.4 as well as EN 50600-2-4:2023-09, chapter 6.4.3.2

 

Lighting:

  • general: EN 50174-2:2018-10, chapter 4.3.2.1
  • in office premises: EN 50174-2:2018-10, chapter 8.3.8.1.3
  • in industrial premises: EN 50174-2:2018-10, chapter 9.3.8 (points to chapter 8.3.8 of the same standard)

 

Environmental conditions (temperature, humidity):

  • in rooms for internet providers: EN 50174-2:2018-10, chapter 4.9.1.3 and appendix D
  • in rooms for service providers: EN 50174-2:2018-10, chapter 4.9.1.4 and appendix D
  • in rooms for distributors in office premises: EN 50174-2:2018-10, chapter 8.3.8.1.5 and appendix D
  • in apartment buildings: EN 50174-2:2018-10, chapter 13.3.8.1.3 and chapter 13.3.8.1.4 and appendix D

Contact

Dirk Träger

Dirk Traeger


Related News

Cabling for 2.5 and 5 Gigabit Ethernet

RJ45 patch cable

Legacy class E cabling and cat. 6 components were designed for Gigabit Ethernet, class EA and cat. 6A are designed for 10 Gigabit Ethernet. But what…

Read more

RJ45 modules for 25 Gigabit Ethernet

Standards

Every now and again one reads about RJ45 modules for 25 Gigabit Ethernet. The frequency range is said to be 1 MHz up to 1250 MHz. However, the…

Read more

IT cabling in meter cabinets for smart metering

Smart Metering

Meter cabinets in the electrical infrastructure must increasingly be equipped with IT cabling for the use of intelligent electricity meters (smart…

Read more

Distributors in the standards

The cabling standards specify cabling and connecting hardware. But they also specify distributors. Read on to find out more.

Read more