To protect the electronic equipment, an appropriate RJ45 surge protection with proper grounding has to be implemented in the cabling link. Telegärtner‘s RJ45-SPD surge protection meets or exceeds the requirements for class EA networks for powerful high speed applications including 10 Gigabit Ethernet and PoE/PoE+. Its integrated protection against overbending the contacts ensures that the link will still work even after a RJ11 or RJ12 connector had been plugged in.
Technical Data
Environment Requirements | |
Operation temperature | -40 to +70° C |
Protection class | IP20 |
Dimensions | |
Hight/Width/Depth | 103/25/63 mm |
Connection | |
IN / OUT | RJ45/RJ11/RJ12 |
Mating cycles | ≥750 |
DIN rail | TS35 |
Transmission Characteristics |
|
Class EA (Permanent / Channel Link) | ISO/IEC 11801, DIN EN 50173-1 |
PoE / PoE+ | acc. to IEEE 802.3at |
Surge Protection | acc. to DIN EN 61643-21 |
Electrical Characteristics | |
Max. continuous operating voltage UC | ≤ 3,3 V DC (60VDC/POE+) |
Nominal current IN | ≤ 1,5 A (25 °C) |
Nominal discharge surge current (8/20)μs core-core / core-ground |
100 A / 2 kA |
Protection level Up core-core / core-ground |
≤ 9 V (B2-1 kV/25 A) / ≤ 600 V |